All Tools View Categories About Contact Privacy

Circuit Breaker Size Calculator

Suggest a preliminary breaker rating from load current, conductor ampacity, continuous-load requirements, system voltage and the selected electrical standard. For planning; final selection follows code.

Circuit load
Enter the running current measured or computed, and the starting current for motors - the frame must ride the surge.
Suggested Breaker
breaker (A)
min wire amps
Notes

About Circuit Breaker Size Calculator

A breaker has one job with two hands: let the circuit run what it must, and cut the power before the cable burns. The tension between those two is why sizing is a calculation and not a guess.

Circuit Breaker Size Calculator turns load current plus continuous-load rules into a suggested breaker rating, showing the required conductor ampacity and checking the motor-start surge where it applies.

It is a planning aid. Final selection must follow the code and the equipment manufacturer requirements in force.

Features

  • Load in kW, A or VA: Enter what the circuit really carries.
  • Continuous load handling: 125% applied to continuous parts.
  • Phase and voltage: Single and three-phase formulas.
  • Power factor: For reactive loads like motors.
  • Conductor check: Minimum ampacity shown for the cable.
  • NEC or IEC: Select the sizing convention.
  • Motor surge note: Where starting current is entered.
  • Export: Copy or download as text, CSV or JSON.

How to Use

  1. Enter the load current (or kW + voltage).
  2. Enter the continuous portion of the load.
  3. Select phase, voltage and standard.
  4. Optional: enter the motor starting current.
  5. Read the suggested breaker size and minimum cable ampacity.
  6. Export the sizing note if needed.

Examples

Example 1 — Heater. 3.68 kW continuous at 230 V, 1P: 16 A at design current, a 20 A breaker.

Example 2 — Mixed. 20 A of continuous and 10 A non-continuous: 35 A design, a 40 A breaker, minimum cable 35 A.

Example 3 — Motor. 11 kW, 20.8 A FLA with a 125 A start: the frame must ride the surge, so a D-curve 32 A breaker protects the running current.

Example 4 — 3-phase. 15 kW at 400 V, pf 0.9: 24.1 A running, 32 A breaker with the right curve.

Benefits

  • Design current correct: Continuous 125% handled automatically.
  • Frame picked: Next standard rating chosen for you.
  • Wire not forgotten: Minimum conductor ampacity shown.
  • Standards aware: NEC or IEC selected explicitly.
  • Free and private: No uploads, no accounts, no logging.

Frequently Asked Questions

How do I size a circuit breaker?
Compute the circuit current, count continuous loads at 125%, and select the next standard breaker rating at or above that value. The breaker must protect the conductor while allowing the load to run.
Why 125% for continuous loads?
Continuous loads run 3+ hours, heating the breaker case and terminals persistently. Design current is therefore 1.25x for continuous plus 1.0x for non-continuous parts, matching the way codes size overcurrent protection.
How are kW converted to amps?
Single-phase: amps = kW x 1000 / (V x pf). Three-phase: amps = kW x 1000 / (1.732 x V x pf). Motors add a starting-surge check beyond the running current.
What standard breaker sizes exist?
Common ratings step at 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160, 200 A and up. The calculator picks the next rating at or above the required amps.
How does the conductor ampacity relate?
The breaker protects the wire: its rating must not exceed the conductor ampacity for most circuits. The calculator shows the required minimum ampacity so you select the cable with it.
NEC or IEC sizing?
The methods align in principle but differ in tables, test curves and device availability. The calculator offers both; the result remains a suggestion to confirm against the code in force.
Is my data stored?
No. Everything runs in your browser; nothing is uploaded, saved or logged.