Examples

Example: 300 mm wide x 100 mm deep ladder tray (50% fill = 15000 mm2 allowed) with ten 25 mm cables (each 491 mm2, total 4910 mm2) -> about 16% tray fill.

Benefits

  • Verify a tray is not overfilled
  • Plan additional cable pulls

Frequently Asked Questions

What is tray fill?
It is the share of the tray cross-section occupied by cables. NEC limits it so cables can be supported and cooled.
What fill percent is allowed?
Typically 50% for ladder and ventilated trays and 40% for solid-bottom trays (for one or more multiconductor cables). The tool uses your selected value.
How are cables measured?
Use the cable outer diameter. Area is treated as a circle: pi/4 x diameter^2.