All Tools View Categories About Contact Privacy

Ground-Fault Calculator

Estimate the ground-fault current and touch voltage for a line-to-earth fault, check whether the protective device (RCD or breaker) would clear it in time, and judge the hazard level.

System
Protection
For a bolted fault leave the contact resistance at 0.
Ground Fault
fault current
touch voltage
Notes

About Ground-Fault Calculator

Most electrical injuries never involve phase-to-phase shorts. They involve a live conductor meeting earth through a broken cable, a damp wall or a person - the ground fault, which does its damage in the half-second before anything clears.

Ground-Fault Calculator estimates the fault current and the touch voltage for a line-to-earth fault, then judges whether the RCD or breaker protecting the circuit would actually clear it in time.

It is a field-aid. Always verify with an instrument (loop tester) and the code in force.

Features

  • Phase voltage: Line-to-earth voltage input.
  • Source impedance: From transformer kVA and %Z.
  • Loop impedance: Phase plus earth conductor path.
  • Fault resistance: Contact resistance at the fault.
  • Touch voltage: Hazard voltage computed directly.
  • RCD check: Trips in time or not, with the reason.
  • Breaker check: Minimum earth-fault current rule.
  • Export: Copy or download as text, CSV or JSON.

How to Use

  1. Set the phase voltage (230 V, 240 V, 120 V...).
  2. Enter the transformer kVA and %Z for the source.
  3. Enter the loop cable length and impedance.
  4. Optional: set the fault contact resistance.
  5. Pick the RCD rating (or none).
  6. Read the fault current, touch voltage and clearance verdict.

Examples

Example 1 — Bolted fault. 230 V, 30 m loop at 8 m-ohm/1000 m: about 190 A faults; a 32 A breaker clears it, a 30 mA RCD trips instantly.

Example 2 — High-resistance contact. Same circuit with a 10 ohm fault: 22 A fault, touch voltage near 220 V near the source side of the contact - still hazardous but too low for the breaker, so the RCD is essential.

Example 3 — Poor earth. Loop impedance doubled by a long earth run: fault current halves, an RCD stays near its clear boundary - time to improve the earth.

Benefits

  • Hazard visible: Touch voltage shown against 50 V.
  • Clearance judged: RCD and breaker verdicts computed.
  • Loop-aware: Cable and earth path included.
  • Field practical: Simple inputs, immediate answer.
  • Private: No uploads, no accounts, no logging.

Frequently Asked Questions

What is a ground fault?
It is an unintentional path from a live conductor to earth - through a damaged cable, water, or a person. The current and the touch voltage decide how dangerous it is and how fast a device must clear it.
How is ground-fault current found?
Divide the phase voltage by the fault loop impedance: the source impedance plus the phase and earth conductors back to the source, plus the fault contact resistance.
What is touch voltage?
The voltage a person could touch across the fault: the fault current times the resistance between the touched part and earth. Below about 50 V AC it is usually considered safe to touch.
How fast must an RCD clear?
A 30 mA RCD in general use trips within about 0.3 s at most, and well within 0.04 s at its relay value under IEC 60364 rules, as long as the fault current exceeds about 5x its rating.
Why does the loop impedance matter?
The fault loop is the cable run from the source through the phase conductor, the fault, and back via the earth conductor. High loop impedance means less fault current and slower (or failed) tripping.
What if the fault current is too low?
An RCD needs roughly five times its rating to trip quickly. If the loop impedance pushes the current below that, the RCD may not clear in time - the cure is a better earth or a shorter, larger run.
Is my data stored?
No. Everything runs in your browser; nothing is uploaded, saved or logged.