All Tools View Categories About Contact Privacy

Generator Sizing Calculator

Estimate the generator capacity required for your loads, accounting for running kW/kVA, the largest motor starting kVA, starting sequence, power factor and reserve capacity.

Running load
Largest motor start
Output
Generator Size
standby kVA
specify kVA
Notes

About Generator Sizing Calculator

A generator has to survive two moments: the steady hum of all loads running together, and that instant when the biggest motor slams in and demands many times its running current. The machine that fits one may fail the other.

Generator Sizing Calculator builds a running-kVA base from your loads, adds the largest motor start as a momentary demand, applies a starting sequence and reserve, and returns the kVA rating to specify at standby and prime duty.

It is a preliminary estimate. Final selection follows the manufacturer rating tables and site conditions.

Features

  • Running loads: Enter total kW and kVA with power factor.
  • Largest motor start: Its starting kVA as the surge test.
  • Starting sequence: Adds starts one at a time or stacked.
  • Reserve capacity: 10-25% headroom applied to the size.
  • Standby and prime: Both duty ratings shown.
  • Current at voltage: The feeder current for the chosen set.
  • Export: Copy or download the sizing as text, CSV or JSON.
  • Learning guide: Why the start wins the sizing argument.

How to Use

  1. Enter the running load in kW and its power factor.
  2. Enter the largest motor starting kVA (or its kW and multiplier).
  3. Choose the starting sequence — single or stacked starts.
  4. Set the reserve percentage for headroom.
  5. Read the generator kVA at standby and prime duty.
  6. Export the sizing sheet if needed.

Examples

Example 1 — Fire plant. 60 kW base at 0.85 pf, 50 kVA largest start, single sequence, 10% reserve: about 110 kVA standby.

Example 2 — Pump station. 100 kW of pumps, largest start 90 kVA, 20% reserve: roughly 230 kVA if starts stack.

Example 3 — Small standby. 25 kW essential load, 15 kVA motor start, 15% reserve: about 48 kVA, size 50 kVA.

Example 4 — Prime. A 150 kVA standby set at 80% derating renders about 120 kVA continuous — confirm the duty curve.

Benefits

  • Both moments covered: Running load and the start surge both checked.
  • Sequence-aware: See the difference between staggering and stacking starts.
  • Duty correct: Standby vs prime ratings kept separate.
  • Explained maths: The kVA build-up shown live.
  • Free and private: No uploads, no accounts, no logging.

Frequently Asked Questions

How do I size a generator?
Add the running kVA of all loads, factor in the largest motor starting kVA with a power factor allowance, decide the start sequence, then apply the desired reserve. The binding figure is usually the running kVA plus the biggest motor start.
Why does the largest motor matter so much?
Starting a motor transiently demands several times its running kVA. If the generator cannot supply the surge without a deep voltage dip, the start may fail or flicker everything else off.
What is starting sequence?
The order loads start. Starting the largest motors one at a time prevents simultaneous inrush. A good sequence only ever stacks one motor start on top of running base load.
What reserve should I allow?
Common practice is 10-25% spare capacity so the set does not run at 100% continuously and can absorb transients. The calculator applies your chosen reserve percentage.
How does power factor affect generator size?
A generator is rated in kVA; the real load is kW. A 100 kW mixed load at 0.8 pf needs 125 kVA of machine. Motor-heavy loads pull the pf down and drive the size up.
Standby or prime?
Standby ratings run briefly during outages; prime power runs continuously. A machine derates for prime duty — roughly 80-90% of its standby kVA — so state which duty you design for.
Is my data stored?
No. Everything runs in your browser; nothing is uploaded, saved or logged.