All Tools View Categories About Contact Privacy

kW to kVA Calculator

Convert real power in kilowatts to the apparent power in kilovolt-amps the supply must provide, at your load power factor. For sizing generators, transformers and UPS systems.

Inputs
Exact pf
Presets load into the exact field below — fine-tune it there.
Apparent Power
kVA required
kVAr reactive
Notes

About kW to kVA Calculator

kW tells you the work a load does; kVA tells you how much current the supply has to carry to do it. For any inductive load the two numbers differ — and it is the kVA that decides the size of generators, transformers, UPS units and cables.

kW to kVA Calculator converts real power up to apparent power at your power factor, showing the reactive kilovolt-amps the load also pulls. The result is the rating number you size equipment on.

Everything runs in the browser; nothing is uploaded.

Features

  • Convert kW to kVA: At any power factor from 0.3 to 1.
  • Reactive component: kVAr shown, so the power triangle is explicit.
  • Load presets: 1.0 resistive, 0.9 electronics, 0.8 classic, 0.7 poor.
  • Live formula: kVA = kW / pf, recomputed as you type.
  • Export: Copy or download as text, CSV or JSON.
  • Learning guide: Why the kVA you buy must exceed the kW you use.

How to Use

  1. Enter the real power in kW.
  2. Select or enter the power factor — 0.8 for mixed loads.
  3. Read the apparent power in kVA the source must provide.
  4. Check the reactive kVAr to understand where the extra goes.
  5. Export the conversion if needed.

Examples

Example 1 — Generator. 80 kW of site load at 0.8 pf needs a 100 kVA generator.

Example 2 — Transformer. 144 kW at 0.9 pf requires a 160 kVA transformer.

Example 3 — UPS. 45 kW of IT at 0.9 pf = 50 kVA UPS.

Example 4 — Motor-heavy. 120 kW at 0.7 pf demands about 171 kVA supply — pf correction would pull that down fast.

Benefits

  • Size equipment correctly: The kVA number you actually order from.
  • Reactive clarity: See the kVAr you are paying to carry.
  • Explained maths: The division shown live in the formula line.
  • Export ready: Text, CSV and JSON for specs and quotes.
  • Free and private: No uploads, no accounts, no logging.

Frequently Asked Questions

How do I convert kW to kVA?
kVA = kW / power factor. A load that draws 80 kW of real power at 0.8 pf needs a 100 kVA supply. The division accounts for the reactive current the load still demands.
Why is kVA bigger than kW?
Because the supply must carry the reactive current as well as the working current. At pf 0.8 the apparent power is 25% larger than the real power. Apparent is always the bigger number below unity pf.
Which power factor should I use?
0.8 is the classic design figure for mixed and motor loads. Resistive loads sit near 1.0; electronics commonly 0.9-0.95. Use the nameplate or measured pf when available.
When do I need kVA instead of kW?
Whenever you size equipment whose rating is in kVA — generators, transformers, UPS, switchgear and cables. The kVA says how much apparent power the gear must handle.
What is the reactive power in this conversion?
If you know the kW and the kVA, the reactive kVAr = sqrt(kVA^2 - kW^2). It is the non-working part the pf discount accounts for.
Can pf lag measurement change my answer?
Yes. The real pf of a busy plant changes through the day. Use the design or worst-case pf so the kVA you size has margin for the reactive dip.
Is my data stored?
No. Everything runs in your browser; nothing is uploaded, saved or logged.