GFCI / RCD Trip-Time Reference Tool

Look up standard GFCI/RCD ratings (10, 30, 100, 300 mA), their trip thresholds and maximum clearing times under IEC 60364 / UL 943, with a quick hazard-level estimate.

Reference Input
Enter the measured earth-leakage current (e.g. from a clamp meter or loop tester) to judge the margin.
Threshold Band
band
x rating
Notes

About GFCI / RCD Trip-Time Reference Tool

An RCD is judged on two numbers: how much leakage it lets through and how fast it lets go. Neither is "as small as possible" - a device that trips on every harmless ripple becomes a nuisance - so the ratings and times are a deliberate band.

GFCI / RCD Trip-Time Reference Tool lists standard ratings, their thresholds and maximum clearing times under IEC 60364 and UL 943, and gives a quick verdict on your measured leakage.

It is a reference aid. The exact device data comes from the manufacturer and the code in force.

Features

  • Standard ratings: 10, 30, 100, 300 mA and more.
  • Threshold bands: No-trip, may-trip and must-trip zones.
  • Trip times: IEC 60364 and UL 943 limits.
  • Types: AC, A, B and S explained.
  • Hazard check: Verdict from your leakage figure.
  • Reference tables: Curated look-up data.
  • Export: Copy or download as text, CSV or JSON.

How to Use

  1. Choose the RCD rating (10 to 300 mA).
  2. Enter the measured or estimated leakage.
  3. Pick the type for context.
  4. Read the threshold band and trip-time expectations.
  5. See the hazard verdict and next step.

Examples

Example 1 — 30 mA circuit. 15 mA measured: between 0.5x and 1x - may trip intermittently, worth finding the leakage source.

Example 2 — 150 mA. Exactly 5x a 30 mA unit: the device must clear within 40 ms.

Example 3 — 300 mA main. 120 mA background leakage: below 0.5x, tolerated, but leave headroom for growth.

Benefits

  • Instant lookup: Thresholds at a glance.
  • Both standards: IEC and UL figures shown.
  • Field verdict: Judge a measurement fast.
  • Type clarity: AC/A/B/S side by side.
  • Private: No uploads, no accounts, no logging.

Frequently Asked Questions

What is a GFCI/RCD?
A residual current device measures the imbalance between live and neutral. Any leakage to earth trips it - protecting people rather than just the cable. The same device is called GFCI in the US and RCD in Europe.
What do the ratings mean?
The mA rating is the nominal residual current (IΔn). A 30 mA RCD must trip at or below 30 mA; it operates fastest around 5x that value, near 150 mA for a 30 mA unit.
How fast must an RCD trip?
For general-purpose (non-delayed) types, IEC 60364 requires tripping within 0.3 s, and faster types within 0.04 s, with the actual trip time shrinking as the residual current grows toward 5x IΔn.
What is a type AC vs A vs B?
Type AC trips on sinusoidal AC leakage. Type A also covers pulsating DC leakage (common with electronics). Type B covers smooth DC - EV charging and similar modern loads.
What is a time-delay (S) RCD?
An S-type (selective) RCD introduces a deliberate delay so the downstream unit trips first. It is used for fire-protection and selectivity schemes, not for personal protection circuits.
How is the hazard level judged?
Leakage under ~0.5x IΔn is usually tolerated. Between 0.5x and 1x the device may or may not trip. Above 1x it must trip; the margin shows how close the circuit is to nuisance or required operation.
Is my data stored?
No. Everything runs in your browser; nothing is uploaded, saved or logged.