Grounding Conductor Size Calculator

Estimate the minimum grounding/earthing conductor size from the phase conductor, protection rating and standard (NEC table-based lookup or simplified IEC /2 principle).

Method
Options
The result is the minimum protective/earthing conductor for typical TN/S conditions. Confirm with the code table and earthing system in force.
Grounding Conductor
NEC EGC
IEC PE
Notes

About Grounding Conductor Size Calculator

Ground is the safety net of the installation - the path that turns a faulted live part into a tripped circuit instead of a shocking one. But the net is only as strong as its thinnest strand, and the thinnest strand is the grounding conductor.

Grounding Conductor Size Calculator estimates the minimum protective/earthing conductor size two ways: the NEC table method keyed to the protection rating, and the IEC /2-principle from the phase cross-section.

It is a planning aid. Final selection follows the code edition and earthing system (TT, TN, IT) in force.

Features

  • Two methods: NEC table lookup or IEC /2 rule.
  • Phase conductor: Enter AWG or mm².
  • Protection rating: Breaker/fuse in amps for NEC.
  • Material: Copper or aluminium.
  • Both results: Show NEC and IEC together.
  • Standard sizes: Nearest conductor bumped up.
  • Export: Copy or download as text, CSV or JSON.

How to Use

  1. Pick the method: NEC (protective device) or IEC (phase cross-section).
  2. Enter the breaker/fuse rating or the phase mm²/AWG.
  3. Choose the material.
  4. Select the standard you will install to.
  5. Read the minimum grounding conductor size.
  6. Confirm with the code table in force.

Examples

Example 1 — NEC. A 60 A circuit: Table 250.122 calls 10 AWG copper equipment grounding conductor.

Example 2 — IEC. A 25 mm² phase conductor protected to 6 mm² minimum: /2 gives 16 mm².

Example 3 — Both. A 40 A branch with 10 mm² phase: NEC gives 10 AWG, IEC /2 rounds to 6 mm².

Benefits

  • Two conventions: NEC and IEC results side by side.
  • Simple inputs: Breaker amps or phase cross-section.
  • Immediate answer: Standard size chosen for you.
  • Material aware: Adjusts for aluminium.
  • Private: No uploads, no accounts, no logging.

Frequently Asked Questions

How is the grounding conductor sized?
For equipment grounding, NEC Table 250.122 keys the minimum size to the overcurrent device rating. For the main earthing conductor, the phase conductor and the earthing system decide the size.
What is the /2 rule in IEC practice?
A common simplification sizes the protective conductor at half the phase conductor cross-section (rounded up to a standard size), with a minimum of 2.5 mm² when mechanically protected.
NEC vs IEC sizing?
NEC table-based rules use AWG/kcmil sized from the breaker or the phase conductor. IEC/EU practice commonly uses the /2 principle in mm². The calculator presents both, based on your choice.
Which leg is the equipment grounding conductor?
The conductor that bonds the non-live metal parts (enclosures, motor frames) to ground. For a 30 A circuit NEC calls a 10 AWG copper equipment grounding conductor, for example.
How big is the main earthing conductor?
It must carry fault current back to the source long enough to trip the device. The calculator uses the phase conductor or the protective-device rating, and you confirm with the code table in force.
Why is the minimum 2.5 mm²?
A protective conductor must survive mechanical abuse and fault current. That is why mechanically protected minimums (2.5 mm² copper in IEC practice) exist below simple electrical sizing.
Is my data stored?
No. Everything runs in your browser; nothing is uploaded, saved or logged.